This is a no common "No cooling" service call.
We arrived to the place and after a detailed inspection we found this electrical issue. We noticed the main circuit breaker for the air handling unit kept tripping and this is why. Notice in the picture the pattern of the issue. The cause was a sharp edge inside the connector that over the years and the vibration produced by the air handler when in operation was eating the insulation of the power wire until it went all the way through.
This is not a common issue but from time to time we find surprises. This is one of them. We cut the damaged part of the wire and installed a new non fuse service disconnect box and a new power wire.
We left the place with our client happy and with the system up, running, cooling and draining okay.
Do not hesitate to give us a call.
Here at North Pole Air Conditioning and Heating Services, Inc. we are ready for any challenge. You won't be disappointed because we are in business to give what you want most: COMFORT at affordable prices.

b2ap3_thumbnail_10457569_650822661675425_8417040436077447512_n_20140623-152450_1.jpgb2ap3_thumbnail_10426896_650822658342092_5590260026879197918_n_20140623-152448_1.jpgb2ap3_thumbnail_10376856_650822711675420_9073177023568554266_n_20140623-152443_1.jpgb2ap3_thumbnail_10413380_650822691675422_8930324779091309023_n_20140623-152446_1.jpgb2ap3_thumbnail_10385583_650822785008746_8830534938327960951_n_20140623-152445_1.jpg